AIR CONDITIONING SYSTEM TROUBLESHOOTING AND TESTING - CONTINUED
0227 00
AIR CONDITIONING SYSTEM TROUBLESHOOTING
Table 1. Problem - Warm Airflow When Air Conditioning Is On.
Possible Cause
Remedy
There is no refrigerant charge in system. Repair any leaks, evacuate system and add a full charge of refrigerant (WP 0297
Moisture in system.
If moisture is in system, ice crystals may form at expansion valve, blocking the
flow of refrigerant (off and on). Recover refrigerant charge (WP 0297 00), evacuate
system, and add a full charge of refrigerant (WP 0297 00).
Table 2. Problem - Low Evaporator Coil Outlet Pressure (Low Compressor Suction Pressure).
Possible Cause
Remedy
The expansion valve is not working
Replace expansion valve (WP 0299 00).
There are restrictions in line to expansion Remove line restrictions.
valve.
There is an insufficient refrigerant charge Locate leak. Recover refrigerant charge (WP 0297 00) and add a full refrigerant
in system.
charge (WP 0297 00).
Table 3. Problem - High Compressor Discharge Pressure.
Possible Cause
Remedy
There is an internal restriction in Replace condenser (WP 0304 00).
condenser. (Ice buildup on the condenser
or a cool spot on the line from the
condenser to the receiver-dryer).
Air is present in system.
Repair any leaks, evacuate system and add a full charge of refrigerant (WP 0297
Restriction in compressor discharge line. Repair or replace line (WP 0305 00).
Table 4. Problem - Evaporator Outlet Air Temperature Increases
as Compressor Discharge Pressure Drops.
Possible Cause
Remedy
The expansion valve setting is too low.
|