AIR CONDITIONING SYSTEM TROUBLESHOOTING AND TESTING - CONTINUED
0018 00
PROBLEM - LITTLE OR NO AIRFLOW
POSSIBLE CAUSE
REMEDY
The blower is not operating.
Check for an open circuit breaker. An open circuit indicates a short in the
electrical system, which must be located and repaired.
Check the air conditioner relays for operation. Replace as necessary.
Make sure the blower motor switch is working. Replace if necessary.
Check the wiring to the blower motor. If any connections are loose, securely
tighten them.
Check the blower motor for operation. Replace if sticking or otherwise
inoperative.
Check the resistor block. Replace if necessary.
CAUTION: Never try to bypass the fuse in the resistor block. To do so could
cause the blower motor to overheat, resulting in serious damage to the heater/air-
conditioning system.
There are restrictions or leaks in the air Examine all air ducts and remove any blockages. Stop any leaks or replace any
ducts.
portion where the leaks cannot be stopped.
Ice has formed on the evaporator coil.
Defrost the evaporator coil before resuming operation of the air conditioner.
PROBLEM - WARM AIRFLOW WHEN AIR CONDITIONER IS ON
POSSIBLE CAUSE
REMEDY
There is no refrigerant charge in the Perform a leak test.
system.
The  refrigerant
is
not Leak test the system.
operating.
Drive belt needs repair or replacement.
The air conditioner microswitch is not Replace the microswitch.
working.
Ice has formed on the evaporator coil.
Defrost the evaporator coil before resuming operation of the air conditioner.
PROBLEM - HIGH COMPRESSOR DISCHARGE PRESSURE
POSSIBLE CAUSE
REMEDY
Airflow  through
the
is Remove the debris from the condenser.
restricted.
Air is present in the system.
Perform a leak test.
Heavy frosting on the suction line Defrost the evaporator coil before resuming operation of the air conditioner.
suggests that the evaporator coil is
flooded.
0018 00-7