ORGANIZATIONAL TROUBLESHOOTING - CONTINUED
MALFUNCTION
TEST OR INSPECTION
CORRECTIVE ACTION
CAUTION
Do not ground voltage regulator to any ac generator terminal. Grounding voltage regulator to ac generator
terminal may cause damage to parts.
Step 7.
Using 5/16inch, 1/4inch drive socket and ratchet handle unscrew and take out two screws (6) and
screw (7). Pull voltage regulator lead (8) off of ac generator terminal (9). Connect ac generator and
voltage regulator test set to ac generator terminals (5 and 9). Check test set ammeter for reading of
1.9 to 2.6 amps for 35 amp ac generators, or 2.0 to 2.5 amps for 55 amp ac generators. Disconnect
ac generator and voltage regulator test set.
a.
If test set ammeter reads as specified, go to step 8.
b.
If test set ammeter does not read as specified, replace ac generator (page 2-436).
TA242737
2-63
|